0755-2790 2267
0755-2790 2204
Ture double-conversion
DSP technology guarantees high performance
Output power factor 1.0
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving(ECO)
Emergency power off function(EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers for long-run model
Maintenanc bypass available
Parallel operation with common battery
Power walk-in function
Optional parallel operation
Optional isolation transformer offers full isolation and complete common mode noise rejection
Product | 30KVA High Frequency Tower Online UPS | |
Capacity | 30KVA/30KW | |
Parallel Capability | UP to 6 units in parallel | |
INPUT | ||
Nominal Voltage | 3*400 VAC(3Ph+N) / 230VAC(1Ph+N) | |
Voltage Range | 110-300VAC@50% load 176-276VAC@100% load | |
Frequency Range | 40 ~ 70Hz | |
Power Factor | ≧0.99@100% Load | |
Harmonic Distortion(THDi) | <4% at full linear load | |
OUTPUT | ||
Output Voltage | 3*360/380/400/415 VAC(3Ph+N) or 208/220/230/240 VAC(1Ph+N) | |
AC Voltage Regulation(Batt. Mode) | ±1% | |
Frequency Range(Synchronized Range) | 46~54Hz or 56 ~ 64Hz | |
Frequency Range(Batt. Mode) | 50 Hz ± 0.1 Hz / 60 Hz ± 0.1 Hz | |
Current Crest Ratio | 3:1(Max ) | |
Harmonic Distortion | ≤2% THD(Linear Load);≤5% THD(Non-linear Load) | |
Transfer Time | AC Mode to Batt Mode | Zero |
Inverter to Bypass | Zero | |
Waveform(Batt. Mode) | Pure Sine Wave | |
Overload Capability | AC MODE | 100-110% for 60 min, 111-125% for 10 min, 125%-150% for 1min; >150% immediately |
BATTERY MODE | 100-110% for 60 min, 111-125% for 10 min, 125%-150% for 1min; >150% immediately | |
BYPASS | ||
Nominal Voltage | 3*380/400/415 VAC(3Ph+N) | |
Voltage Range | -30%~+20%(Adjustable) | |
Frequency Range(Synchronized Range) | 46~54Hz or 56 ~ 64Hz | |
Overload Capability | >130% 1 minute(default); Continuously working until breaker protection(Optional) | |
EFFICIENCY | ||
AC Mode | 95.50% | |
ECO Mode | 98.50% | |
BATTERY Mode | 94.50% | |
BATTERY | ||
Long-run Model | Battery Type | Depending on the applications |
Numbers | +/-16 pcs ~ +/- 20 pcs(Adjustable) | |
Charging Current(Max.) | 1A~12A(Adjustable) | |
Charging Voltage | +/-13.65V*N(N=16~20) | |
INDICATORS | ||
LCD Panel | UPS Status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
PHYSICAL | ||
Long-run Model | Dimension D*W*H(mm) | 815*300*1000 |
Net Weight(kgs) | 60 | |
ENVIRONMENT | ||
Operation Temperature | 0~ 40℃ | |
Operation Humidity | <95% and non-condersing | |
Altitude | 0~ 1500m at full load | |
Noise Level | Less than 63dB @ 1 Meter | |
MANAGEMENT | ||
Smart RS-232 / USB | Supports Windows Family, Linux and MAC | |
Optional SNMP | Power management from SNMP manager and web browser | |
If output voltage is set as 3×360VAC, the output power of the unit will be de-rated to 90% If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m. Product specifications are subject to change without further notice. |